Analogue output, Digital outputs – Xylem Magflux Electromagnetic Flow Meter User Manual

Page 29

Advertising
background image

29

Electromagnetic Flow Meter

FW: 842018/842009

Analogue Output

The analogue output is an active output with a max. load of 800Ω.

Analogue Output

Terminal

Designation

AO

+

4-20 mA

AO

-

4-20 mA

The analogue output can be programmed for indication of:

-

direct flow

-

inverse flow

-

bidirectional flow

-

absolute flow

See details on pages

63

-

66

incl.

Digital Outputs

MagFlux

®

has two digital outputs - DO 1 with an opto (light triggered)

relay and DO 2 with a mechanical relay.
They can both be programmed for the following functions:

-

high and low flow alarms

-

pulse output for counters R Totalizer Forward and Reverse

-

batch 1 and batch 2 counters

-

system error alarm

-

empty pipe alarm

-

flow direction indication

Opto Relay (DO1)

Terminal

Designation

DO 1

Com

Max. 50 V DC /120 mA

DO 1

NO

Mechanical Relay (DO2)

Terminal

Designation

DO 2

Com

Max. 50 V DC /1 A

DO 2

NO

DO 1 shares the common terminal (Com) with DI.