Electromagnetic Flow Meter
FW: 842018/842009
Analogue Output
The analogue output is an active output with a max. load of 800Ω.
Analogue Output
Terminal
Designation
AO
+
4-20 mA
AO
-
4-20 mA
The analogue output can be programmed for indication of:
-
direct flow
-
inverse flow
-
bidirectional flow
-
absolute flow
Digital Outputs
MagFlux
®
has two digital outputs - DO 1 with an opto (light triggered)
relay and DO 2 with a mechanical relay.
They can both be programmed for the following functions:
-
high and low flow alarms
-
pulse output for counters R Totalizer Forward and Reverse
-
batch 1 and batch 2 counters
-
system error alarm
-
empty pipe alarm
-
flow direction indication
Opto Relay (DO1)
Terminal
Designation
DO 1
Com
Max. 50 V DC /120 mA
DO 1
NO
Mechanical Relay (DO2)
Terminal
Designation
DO 2
Com
Max. 50 V DC /1 A
DO 2
NO
DO 1 shares the common terminal (Com) with DI.