VN-Matrix 300 • Firmware, License Upgrades, and User Accounts

55

2.

Click the

Upload

button to begin uploading the file to the VN-Matrix 300 controller.

This may take a few minutes.

Once the file is uploaded, you can begin installing it into each unit , starting with the
controller unit.

1.

From the

Device List

page, click on the VN-Matrix 300 unit that you want to

upgrade.

2.

From the

Device

page click the

Upgrade

tab. The

Upgrade

page will appear.

3.

Click the

Select Firmware Version

listbox and choose the new firmware file you

want to install. Usually there will only be one file listed.

The remainder of the installation procedure is achieved using the

forward

and (if necessary)

reverse

buttons, to move the installation between the various stages. The current stage/

status is indicated by the

Device Upgrade Status

field.

The process allows you to temporarily install and test the new firmware and, if everything is
OK, you can then permanently install (commit) the new firmware. Up until the last stage it is
possible to return to the existing firmware version.

Figure 40.

Temporarily, Testing, and Permanently Installing New Software

1.

Click the

forward

button. The

Device Upgrade Status

field will show

PREPARE

and

percentage progress. This stage may last a few minutes.

TIP: The chosen firmware version is confirmed in the Upgrade Version field.

2.

When

READY TO ACTIVATE

appears, click the

forward

button again.

3.

The unit will then reboot.
Once rebooted the

Device Upgrade Status

field will show

READY TO COMMIT

and

the VN-Matrix 300 will be using the new firmware. Test for correct operation.

4.

If everything is working correctly, click forward again to permanently install the new
firmware.
The

Device Upgrade Status

field shows

Committing

and percentage progress. This

stage may last a few minutes.
If you experience any problems, click

reverse

to return to the previous stage.

5.

When the Device Upgrade Status field returns to

WAIT

the unit is ready for use.