TroubleShooting & Maintenance

Page

5 - 3

5

TABLE 5 - 1 (C

ONTINUED

... )

ALARMS & ERROR MESSAGES

Keep accurate and dated records, or printouts, of all alarms — when they happen and
when they clear.

Contact your Tank Sentinel service provider if the same alarms occur

often or repeatedly... multiple alarms are not normal.

NOTE

NOTE: Diagnostic text in the left column, is shown bolded { become alarms if active for 48 hours }

#

Printed / Faxed / Displayed
Alarm / Warning Text:

Alarm Type:

System WARNING / Error Descriptions and
ALARM Descriptions

(actions to take)

23

AUXILIARY INPUT

SENSOR

Auxiliary input detected on channel 1 or 2

(follow

policy procedure at your site).

24

CPM LOW CURRENT

SENSOR

Current of Rectifier dropped below the threashold
value (a Tank Sentinel setting) (follow
policy procedure at your site)

25

DRY WELL

SENSOR

TSP-MWS ground water Monitoring Well
BriteSensor is not submerged in water @ Channel
#N

(it cannot detect a product leak unless it's

submerged in ground water... the well may not be
deep enough or the sensor long enough... contact
service provider)

26

EXTERNAL INPUT

SENSOR

External N input module has detected an input
signal

(follow policy procedure at your site).

27

HIGH BRINE

SENSOR

TSP-HIS BriteSensor @ Channel #N detected a
High Brine level

(Call service provider [to confirm

leak] and call your local Regulatory agency. Shut
down pump & dispenser if a leak test has failed on
that tank and see procedures at your site.)

28

LIQUID DETECTED / LIQUID

SENSOR

Standard Sensor @ Channel #N detected a liquid
(run a tank leak test [depending on the sensor
location] and call service provider to identify the
liquid and retest sensor)

29

LOW BRINE

SENSOR

TSP-HIS BriteSensor @ Channel #N detected a
Low Brine level

(Call service provider [to confirm

leak] and call your local Regulatory agency. Shut
down pump & dispenser if a leak test has failed on
that tank and see procedures at your site.)

30

PRODUCT PRESENT /
PRODUCT DETECTED

SENSOR

TSP-DIS, -DDS, -DTS, -MWS BriteSensor @
Channel #N detected Product / leak

(Call service

provider [confirm leak] call the local Regulatory
agency. Shut down pump & dispenser for that
tank and see procedures at your site. [replace
sensor])

31

STANDARD ALARM /
STANDARD INPUT

SENSOR

A Standard Sensor (type TSP-EIS, -HLS, -ULS) @
Channel #N has detected liquid

(run a tank leak

test [depending on the sensor location] and call
service provider to identify the liquid and retest
sensor)