32

SUMP FULL

SENSOR

TSP-DDS, -DTS BriteSensor @ Channel #N
liquid... Sump Full alarm

(see site policy about

pumping containment sump waste water)

33

VAPOR DETECTED / VAPOR

SENSOR

TSP-DVS BriteSensor @ Channel #N detected
product Vapor in the vapor monitoring well

(Call

service provider [to analyze the leak], call your
local Regulatory agency, and see procedures at
your site.)

34

WATER DETECTED

SENSOR

TSP-DIS*, -DDS, DTS, DVS* BriteSensor @
Channel #N detected Water, some sensors* may
not be able to detect product when water is
present

(see procedures at your site)

35

ALPHA ERROR / ALPHA ERR
/ ALPHA V

SYSTEM

Error in API temperature compensation calculating
ALPHA (check any Special Products -- reprogram
temperature compensation type & API ALPHA
value).

36

API ERROR / API VOL

SYSTEM

Error in API temperature compensation routine
(check any Special Products -- reprogram
temperature compensation type).

37

CPM FAILURE

SYSTEM

No Power / Power is below 5 VDC - Check Power
Supply / Increase Voltage (if possible)

38

CPU CRASH

SYSTEM

WARNING - Central Processing Unit / hardware
failure / power quality problem

39

DATA ERROR / DIM

SYSTEM

Transient communication error between the Tank
Sentinel and TS-DIM unit. This alarm/error will
clear itself automatically.

40

DATA NOT AVAILABLE / DIM

SYSTEM

Transient alarm/error caused when TS-DIM unit is
'busy' performing another task and cannot make
the requested data available until it is not 'busy'.
This alarm/error will clear itself automatically.

41

DIM COMM FAILURE

SYSTEM

Tank Sentinel has lost communications with the
TS-DIM unit. Verify power to the DIM / Verify
proper connection between DIM and console.

42

F14 OPEN / F14 FUS

SYSTEM

WARNING - FUSE F14 is blown... no 5 VDC
Sensor Supply Power. Leak detection sensors are
not working and cannot work without power

(call

service provider immediately to replace F14)

43

FAX HARDWARE FAILURE /
FAX HW FAIL / FAX FAL

SYSTEM

WARNING - Fax Hardware Failure... alarms &
compliance faxes cannot be sent

(call service

provider ASAP)