Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, 508 & 750) Installation User Manual
Page 38

6
Page
6 - 4
TANK SENTINEL
®
INSTALLATION GUIDE
Recording RTD/Temperature Sensor Locations
RTD/Temperature sensors measure the temperature of the product. The Tank
Sentinel uses the number and position of these temperature sensors within each
probe for precise volumetric calculations.
For “special” length probes that are not listed in TABLE 2.1:
accurately
record the RTD/Temperature Sensor Locations in this section. Skip this step if
you are not installing a special length probe.
Sensor number 1 is always at the bottom of the probe shaft, which will be the
smallest number listed on the Serial No./Model No. label at the probe head. INCON
probes have 5 temperature sensors (standard), but up to 6 are possible.
This information is required to program the console to work with a “special” length
probe (one that is not listed in TABLE 2.1 of this manual), or with a probe that has
6 RTDs.
Locations are not required when
TSP-LL2-__I inventory only probes are used.
RTD/Temperature Sensor Locations for Special Probes
RTD #
– Probe 1
RTD #
– Probe 2
6
6
5
5
4
4
3
3
2
2
1
1
RTD #
– Probe 3
RTD #
– Probe 4
6
6
5
5
4
4
3
3
2
2
1
1
NOTE
NOTE
NOTE