Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, 508 & 750) Installation User Manual
Page 74

SYSTEM WIRING
Page
7 - 31
7
TABLE 7-5
I/O Input and Output Modules – Model Type –
(
T2
)
Order
INCON P/N
MODULE TYPE
DESCRIPTION
AD14ØI
AC/DC Input Module
90 - to - 140 Volt AC or DC
*
AD24ØI
AC/DC Input Module
180 - to - 240 Volt AC or DC
*
DC28I
DC Input Module
2.5 - to - 28 Volt DC
DC32I
DC Input Module
12 - to - 32 Volt DC
DC6ØI
DC Input Module
35 - to - 60 Volt DC
AC12ØNO
AC Output Module
12 - to - 120 Volt AC
Normally Open
AC24ØNO
AC Output Module
24 - to - 240 Volt AC
Normally Open
AC24ØNC
AC Output Module
24 - to - 240 Volt AC
Normally Closed
DC6ØNO
DC Output Module
5 - to - 60 Volt DC
Normally Open
DC2ØØNO
DC Output Module
5 - to - 200 Volt DC
Normally Open
DRYCONNO
Dry Contact Output Module
Form A
SPST
Normally Open
DRYCONNC
Dry Contact Output Module
Form B
SPST
Normally Closed
CAUTION
The TS-IEM terminal strip is rated for 1 Ampere maximum. DO
NOT exceed this rating — regardless of the module rating !
*
Indicates dual purpose AC/DC Input I/O modules
Output and Dry Contact (Relay) modules are equipped with replaceable fuses...
these fuses are identical but differ between manufacturers. Supply varies with
availability.