Manifold data – Franklin Fueling Systems TS-5000 evo MODBUS Installation & Setup User Manual

Page 12

Advertising
background image

12

Tank Alarms Register

Bit #

Status Bit

0

High High Product 

1

High Product

2

High Water

3

Low Product

4

Low Low Product

5

Precision Leak Detected

6

Gross Leak Detected

7

SCALD Leak Detected

8

Product Density High Limit Exceeded

9

Product Density Low Limit Exceeded

10

Float Missing

11

Probe Synchronization Error

12

No Probe Detected

13

Float Height Error

14-31

Reserved

Manifold Data

Manifold Data Register Set

Manifold Register Start Address = (ManifoldNumber-1)*26+3200

Register Description

Address Offset

Data Format

Resolution

Manifold Status Register

0, 1

See Manifold Status Register

Manifold Alarms Register*

2,3

See Manifold Alarms Register

Temperature

4,5

Signed 32-bit Integer

See Volume Units

Gross Product Volume

6,7

Signed 32-bit Integer

See Volume Units

Net Product Volume

8,9

Signed 32-bit Integer

See Volume Units

Water Volume

10,11

Signed 32-bit Integer

See Volume Units

Ullage Volume

12,13

Signed 32-bit Integer

See Volume Units

Reserved 

14-20

N/A

*Note that this register does not contain all possible alarms for a tank.

Manifold Status Register

Bit #

Status Bit

0

Manifold in Alarm 

1

Delivery in Progress

2-31

Reserved

Manifold Alarms Register

Bit #

Status Bit

0

Low Product

1

Low Low Product

2

SCALD Leak Detected

3-31

Reserved