Franklin Fueling Systems TS-5000 evo MODBUS Installation & Setup User Manual

Page 9

Advertising
background image

9

Modbus Register Map

Register Values
Little Endian Ordering
All 32-bit values are stored such that the least significant bits are in the lower of the 2 register addresses (a.k.a. Little 

Endian). For example, Tank 1 Product level is stored in registers 204 and 205. If the value happened to be large enough 

that it spanned 2 registers, say 9876.5 gallons, the values would be stored as follows:
Gallons resolution is 0.1, so the floating point value is multiplied by 10 and converted to the integer value 98765. In hex, 

this value is 0x000181CD. Mapping this into registers:
Address 204:  0x81CD
Address 205:  0x0001
Two’s Complement Integer Representation

Negative values are stored as 2’s complement values. So, for the sake of a simple example let’s say we had -9876.5 

gallons. The 2’s complement value of -98765 in hex is 0xFFFE7E33.  By noting the highest bit is a 1, you know the 

number is signed. To get the positive value you simply invert the bits and add 1, getting you back to 0x000181CD. This will 

be set up in the Modbus client software.
The following is a table of Input Register addresses that can be accessed using function code 0x04.

Register Mapping Overview

Register Addresses

Data Set

Data Type

100-107

System Units

System Unit Setting 

200-235

Tank 1

Tank 1 Data 

236-271

Tank 2

Tank 2 Data

272- ….

Tank 3 …

Tank 3 Data …

2756-2791

Tank 72

Tank 72 Data

2792-3199

Reserved

3200-3225

Manifold 1

Manifold 1 Data

3226-3251

Manifold 2

Manifold 2 Data

3252-….

Manifold 3…

Manifold 3 Data…

4110-4135

Manifold 36

Manifold 36 Data 

4136-4499

Reserved

Reserved

4500-4501

2-Wire Sensor 1

2-Wire Sensor 1 Data

4502-4503

2-Wire Sensor 2

2-Wire Sensor 2 Data

4504-….

2-Wire Sensor 3…

2-Wire Sensor 3 Data …

4642-4643

2-Wire Sensor 72

2-Wire Sensor 72 Data

4644-4799

Reserved

Reserved

4800-4802

3-Wire Sensor 1

3-Wire Sensor 1 Data

4803-4805

3-Wire Sensor 2

3-Wire Sensor 2 Data

4804-….

3-Wire Sensor 3...

3-Wire Sensor 3 Data …

4941-4943

3-Wire Sensor 48

3-Wire Sensor 48 Data

4944-4999

Reserved

Reserved

5200-5206

Mag Sensor 1

Mag Sensor 1 Data

5207-5213

Mag Sensor 2

Mag Sensor 2 Data

5214-….

Mag Sensor 3…

Mag Sensor 3 Data

5697-5703

Mag Sensor 72

Mag Sensor 72

5704-5899

Reserved

Reserved

5900-5901

PS Relay 1

PS Relay 1 Status

5902-5903

PS Relay 2

PS Relay 2 Status

5904-5999

Reserved

Reserved

Advertising