Sensor data – Franklin Fueling Systems TS-5000 evo MODBUS Installation & Setup User Manual

Page 13

Advertising
background image

13

Sensor Data

2-Wire Sensor Status Register

2-Wire Sensors Start Address = (SensorNumber-1)*2+4500

Bit #

Status Bit

0

Sensor State 

1-31

Reserved

2-Wire Sensor State Table

Bit Value

Sensor State

0

Ok

1

Alarm

3-Wire Sensor Register Set

3-Wire Sensors Start Address = (SensorNumber-1)*3+4800

Register Description

Address Offset

Data Format

Sensor Type

0

See 3-Wire Sensor Type Table

Sensor State

1

See 3-Wire Sensor State Table

Reserved

2

3-Wire Sensor Type Table

Register Value

Sensor Type

0

Unknown Sensor

1

Interstitial (EIS) OR 2-Wire Sensor

2

Discriminating Interstitial Sensor (DIS)

3

Discriminating Dispenser Sump Sensor (DDS)

4

Discriminating Turbine Sump Sensor (DTS)

5

Monitoring Well Sensor (MWS)

6

Hydrostatic Interstitial Brine Reservoir Sensor (HIS)

7

Discriminating Monitoring Well Vapor Sensor (DVS)

3-Wire Sensor State Table

Register Value

Sensor State

0

Ok

1

Alarm

2

Sensor On

3

Product Detected

4

Water Detected

5

Sump Full

6

Dry Well

7

High Brine

8

Low Brine

9

Vapor Detected

10

Vapor Sensor Malfunctioning

11

Temperature Error

12

Synchronization Error

13

Signal Lost

14

ID Error

15

Data Error