Turbine Pump Interface (TPI) Data
TPI Controller Status Register
TPI Start Address = (TPINum-1)*2+6400
Bit #
Status Bit
0
Pump Status
1
Pump Forced Off
2
Pump Controller Faulted
3-15
Reserved
Pump Status Table
Register Value
Pump Status State
0
Idle
1
Running
Pump Forced Off State Table
Register Value
Pump Forced Off State
0
Ok
1
Force Off
Pump Controller Faulted Table
Register Value
Pump Controller Faulted State
0
Ok
1
Controller Faulted
Input Data
Low Voltage Inputs Status Register
LVI Start Address = (LVINum-1)*2+6600
Bit #
Status Bit
0
Input Status
1-15
Reserved
Low Voltage Input Status Table
Bit Value
Low Voltage Input State
0
In-Active
1
Active
AC Input Status Register
DHI Start Address = (DHI Num-1)*2+6700
Bit #
Status Bit
0
Input On
1-15
Reserved
AC Input Bit Value Table
Register Value
AC Input State
0
In-Active
1
Active