Mag sensor register set, Relay data – Franklin Fueling Systems TS-5000 evo MODBUS Installation & Setup User Manual
Page 14
Advertising

14
Mag Sensor Register Set
Mag Sensors Start Address = (SensorNumber-1)*7+5200
Register Description
Address Offset
Data Format
Product Level
0,1
Signed Integer (See Length Units)
Water Level
2,3
Signed Integer (See Length Units)
Status Register
4
See Mag Sensor Status Register
Reserved
5-8
Mag Sensor Status Register
Bit #
Status Bit
0
Water Warning Active
1
Water Alarm Active
2
Product Alarm Active
3
Installation Alarm Active
4
Sensor Missing Alarm Active
5
Sensor Sync Alarm Active
6
Sensor Float Missing Active
7-15
Reserved
Relay Data
Relay Status Register
PS Relay Start Address = (PSRelay-1)*2+5900
Relay Start Address = (Relay-1)*2+6000
Bit #
Status Bit
0
Relay Status
1-15
Reserved
Relay Status State Table
Bit Value
Relay State
0
Deactivated
1
Active