Propane Safety Notes

1. Never overfill your LP-gas container. LP–gas containers not

containing a fixed liquid level gauge must be filled by
weight to 80% of their total capacity. Propane expands
1.5% for each 10 °F increase in temperature. 20% of the
container must remain available for expansion. Some tanks
supplied by Alpha Technologies come equipped with auto-
matic stop fill valves. Tanks must be filled in accordance
with manufactures, D.O.T, NFPA Code 58, state and local
regulations.

2. Do not use pliers to close the POL valve on your tank.

These valves are designed to be closed leak tight by hand or
screwdriver as appropriate. If pliers are needed to stop a
leak , the valve needs replacement.

3. When tightening the POL Nut (left-hand thread) on the

service valve, draw it up snug with a proper wrench – do not
jam it. No thread sealant is necessary. Check for leaks
after connecting, by using a leak detection solution or soapy
water.

4. If you take your LP-gas tank to a LP-gas dealer for filling,

transport it in the proper position in which it is used (verti-
cal for all Alpha Technologies supplied tanks), with the
valves closed and the POL plug inserted. Secure the tank
against falling or rolling.

5. The outside of the tank should be kept corrosion free by

periodic checks and a coat of paint should be used if needed
(light reflective color).