2.0, Installation, continued

2.4

Assembling the Conduit, continued

In the PWE-SG enclosure, using the provided Anderson connectors, terminate the battery

7.

cable. See Fig. 2-9.
If you are installing a battery heater mat, terminate the battery heater mat line cord with

8.

the receptacle provided. See. Fig. 2-10

Fig. 2-9, Attaching Anderson

Connectors to Battery Cables

Fig. 2-10, Receptacle for

Battery Heater Mat Line Cord

White or blue to silver contact

Green to ground

Black or brown to gold contact

Carefully run the upper wires through the drilled hole in the legacy enclosure.

9.

Using the plastic locknut, attach the upper conduit connector. Use channel locks to

10.

carefully tighten the connector, sealing the black rubber O-ring securely against the

enclosure. See Fig. 2-11
The conduit is in place. Optimally, the conduit connectors should be swiveled to 45°F.

11.

See Fig. 2-12.

Fig. 2-11, Attaching Connector

Black O-ring secured

against enclosure

Fig. 2-12, Conduit in Place