Alpha Technologies PWE-SG Series User Manual

Page 22

Advertising
background image

033-090-C0-001, Rev.A

22

2.0

Installation, continued
2.6

Battery Installation, continued

2.6.4 Battery Assembly for Front Terminal Battery Posts

Below is the typical battery terminal assembly for front terminal battery posts. Torque

rating for all terminals in 60-in-lbs (6.5nM).

Bolt

Lock Washer

Flat Washer

Ring Terminal

Threaded Battery Post

Fig. 2-17, Typical Ring Lug Assembly for Front Terminal Batteries, Single Lug

2.6.5 Battery Installation for Front Terminal Batteries

Place the batteries, with the terminals oriented toward the front of the enclosure.

1.

Use the battery manufacturer's recommended spacing between batteries for

maximum ventilation.
Number the batteries using labels or masking tape and record each battery's

2.

number and date code in the maintenance log. This helps in future record

keeping and identification.
Connect the batteries in series to achieve 36VDC or 48VDC.

3.

Verify battery polarity and install battery jumper bars after attaching all terminals

4.

to respective terminal posts. Use a voltmeter to verify polarity and DC voltage at

the module's battery connector.
Plug the battery cable connector into the battery cable connector from the conduit

5.

kit. See page 23 for battery wiring diagrams.

NOTE:

The cables are marked with a RED sleeve to indicate the (+) positive battery terminal.