2.7 Installing Optional Features

Tamper Switch

Jumper Board

Fig. 2-22, Tamper Switch Jumper Board, Legacy Enclosure

2.7.1 Installing the Tamper Switch

The tamper switch provides a magnetic door switch which plugs into the power

supply. Most status monitoring systems provide an alarm if the enclosure door is

opened. Tamper switches are available as normally open (NO) or normally closed

(NC). See Table 1-2 for part numbers and additional information.
In the legacy enclosure:

Using the velcro provided, attach the tamper switch jumper board to the right wall

1.

of the enclosure. See Fig. 2-22.
Unplug the existing tamper switch from the power supply and plug it into the

2.

tamper switch jumper board.
Plug in the new tamper switch extension (coming from the conduit) into the

3.

tamper switch jumper board. Make sure to coil and zip-tie excess wire.
Plug the new tamper switch jumper cable into both the tamper switch jumper

4.

board and the power supply.

NOTE:

The instructions in this section presuppose that you have already placed the appropriate lines in the conduit.

This is a pre-requisite for installing these features. See Section 2.4 for information on assembling the conduit.