3.2 Technical characteristics

(a)

15 °C - 1013 mbar

(b)

In order to measure the ionization current, take out the ionization

cable connector and insert a micro-ammeter.

(c)

According to the national standard (possible adaptation of the two

diameters).

(d)

Availability in line with the country's sales plan.

(e)

Underload on GZ350 gases and H-13 mbar
See: Leaflet on conversion to another gas

1 mbar = 100 Pa

Models DTG ... Eco.NOx

133

(d)

134

135

136

137

138

(d)

139

(d)

Nominal output Pn

kW

12

18

24

30

36

42

(e)

48

(e)

Power input

kW

13.4

20.1

26.7

33.3

39.9

46.4

52.9

Gas flow rate

Natural gas H/E

(a)

GZ50

m

3

/h

1.42

2.13

2.83

3.52

4.22

4.91

5.60

Natural gas L/LL

(a)

m

3

/h

1.65

2.47

3.29

4.10

4.91

5.71

6.51

H - 13 mbar m

3

/h

1.42

2.13

2.83

3.52

4.22

4.79

5.13

GZ350

(a)

m

3

/h

1.97

2.95

3.92

4.89

5.87

6.50

7.29

GZ410

(a)

m

3

/h

1.71

2.56

3.41

4.25

5.09

5.92

6.75

Propane Kg/h

1.04

1.56

2.07

2.59

3.10

3.60

4.11

Number of cast iron parts

3

4

5

6

7

8

9

Number of nozzles

2

3

4

5

6

7

8

Mass flue gas flow rate (H/E)

Kg/h

48

53

70

81

97

109

120

Smoke temperature

°C

100

120

125

130

133

135

135

Minimal ionization current

(b)

µA

0.3

0.3

0.3

0.3

0.3

0.3

0.3

Required depressurisation at the nozzle

mbar

0.05

0.05

0.05

0.05

0.05

0.05

0.05

Min water temperature

°C

30

30

30

30

30

30

30

Max water temperature

°C

90

90

90

90

90

90

90

Maximum admissible operating pressure

bar

4

4

4

4

4

4

4

Electrical connection

V/Hz

230-50

230-50

230-50

230-50

230-50

230-50

230-50

Absorbed electrical power

W

12

12

12

12

12

12

12

Gas connection

inch

R 1/2

R 1/2

R 1/2

R 1/2

R 3/4

R 3/4

R 3/4

Water connection

inch

R 1

R 1

R 1

R 1

R 1

R 1

R 1

Smoke connection (internal diameter)

mm

110/111

(c)

110/111

(c)

125/130

(c)

150/153

(c)

150/153

(c)

150/153

(c)

180

Water content

l

7.1

8.8

10.5

12.2

13.9

15.6

17.3

Loss of hydraulic circuit load at

T = 15 K

mbar

4

8

15

23

33

46

60

Net weight

kg

87

100

118

135

153

162

183

Shipping weight

kg

97

113

133

148

166

181

203