4 filling the system, Boiler self-standing, With domestic hot water tank – DE DIETRICH ELITEC DTG 130 Eco.Nox User Manual

Page 22: 5 water treatment, 5 gas connection, France, Other countries

Advertising
background image

22

DTG 130 Eco.NOx

01/02/11 - 300002915-001-E

4.4.4

Filling the system

„

Boiler self-standing:

The installation must be filled via the draining/filling valve. Check that
the entire installation has been correctly bled.

„

With domestic hot water tank:

Z

See: Domestic hot water calorifier instructions.

4.4.5

Water treatment



Central heating systems must be cleaned to eliminate
debris (copper, strands, brazing flux) linked to the
installation of the system and deposits that can cause
malfunctions (noise in the system, chemical reaction
between metals). On the other hand, it is important to
protect central heating systems against corrosion, scaling
and microbiological growth by using a corrosion inhibitor
adapted to all types of systems (steel, cast iron radiators,
heated floor, PER)

Switzerland: The water quality must comply with the SICC directives
No. 97-1F "Treatment of water intended for heating, steam,
refrigeration and air conditioning installations".

4.5 Gas connection

It is necessary to abide by the prevailing instructions and regulations.
Each time, a blocking tap will be located as near as possible to the
heater. A gas filter must be fitted to the boiler inlet.
The load loss between the meter and heater must be lower than 1
mbar (heater operating).

„

France

Pipe diameters must be defined in accordance with ATG's
(Association Technique de Gaz) B171 specifications.

„

Other countries

The diameters of the pipes must be defined in accordance with the
standards in force in your country.