Assembly and disassembly

7

ASSEMBLY AND DISASSEMBLY

7.1 Safety instructions

DANGER!

Risk of explosion!

Following installation, solenoid coil and valve body form a closed

system. If used in the explosion-risk area, there is a danger of

explosion if the system is opened during operation!

▶ The system must not be disassembled during operation.
Risk of short-circuit!

Damaged connection lines may cause a short-circuit.

▶ The connection lines for the coil must be laid permanently and

protected against damage.

Risk of burns/risk of fire during long-term operation!

The solenoid coil may become very hot during long-term operation.

▶ Take hold of a device which has been running for a prolonged

period with protective gloves only.

DANGER!

Risk of electric shock!

There is a serious risk of injury when reaching into the equipment.

▶ Live terminals in the terminal box may cause an electric shock,

short-circuit or explosion. Switch off the power supply. Only then

open the terminal box.

▶ The connection lines of the electromagnets must be permanently

installed in such a way that they are adequately protected from

mechanical damage.

▶ Only trained electrical engineers may work on the electrical system.

▶ Before starting work, always switch off the power supply and

safeguard to prevent re-activation!

▶ Observe applicable accident prevention and safety regulations

for electrical equipment!

WARNING!

Danger – high pressure!
When reaching into the system, there is an acute risk of injury.

▶ Only skilled and instructed personnel may work on the system

with suitable tools.

▶ Before disconnecting lines and valves, switch off the pressure

and bleed the lines.

▶ Observe applicable accident prevention and safety regulations

for pressurized devices.

▶ After an interruption in the power supply or fluid supply, ensure

that the process is restarted in a defined or controlled manner.

▶ During installation note the flow direction.

DANGER!

▶ The operator must ensure an adequate strain relief.

▶ Lines with an outer diameter of 6 mm ... 13 mm can be used.

Observe the maximum thermal load of the installed cables and

lines.

▶ The inserted break-out seal must be adjusted to the diameter of

the cable/line.

▶ The rated cross-section of the cables/line cores must be at least

0.75 mm² and must not exceed 2.5 mm².

▶ Screws for attaching the cover of the terminal box must be tight-

ened to a torque of 100 Ncm (±5%).

english

PTB 00 ATEX 2202 X