3 installation conditions – Burkert Type 2834 User Manual

Page 9

Advertising
background image

9

Application conditions

• For use in gas pumps:

Metal (brass, aluminum, stainless steel)

• Other applications:

Metal (brass, aluminum, stainless steel) or plastic
(e.g. polyamide PA 6 GV...)

Sheathing of the electrical connection lines:
• For terminal box design:

without connection line

• For cable design:

Rubber hose

5.2.2 Minimum dimensions

Valve body:
56 mm x 49 mm x 36 mm (L x W x H)
A larger valve body with improved thermal conductivity may
be used at any time.

5.2.3 Operating temperature range:

DANGER!

Risk of explosion!
If the max. permitted temperature values for the coil Type 7..-... are
exceeded, there is a danger of explosion.

▶ It is essential to observe the temperature specifications for the coil.

▶ Observe any restrictions by the max. permitted values for the

solenoid valve combined with the coil.

Type designation

71.

72.

73.

735

Nominal voltage [V]

12 ... 380

Current type

AC/DC

Rated current

0.012

... 0.38

0.038

... 1.2

0.017

... 0.53

0.013

... 0.42

Nominal power (W)

5

15

7

6

Temperature class

T6

T4

T6

T6

Ambient temperature (°C)

–40 ...

+60

–40 ...+40

Voltage tolerance (%)

±10%

±20%

5.3 Installation conditions

The solenoid coils Type 7..-... are suitable for individual assembly only.
The connection lines must be laid permanently to protect against
damage.

Also observe the specifications in the chapter entitled “Tech-
nical data”
.

english

PTB 00 ATEX 2202 X