FieldbusmodulePROFIBUSDP/V1
8.
FIELD BUS MODULE PROFIBUS DP/V1
8.1.
PROFIBUS DP/V1, IP20 - overview
Power Supply
LED Status Display
Field bus connection
Functional earth
DIP Switches
Connection for RIO
slave bus module –
Figure 6:
Overview of field bus module PROFIBUS DP IP20
The DIP switches can be operated through the covering film.
8.1.1.
Power supply IP20
The 4-pole plug-in connector for the power supply is configured as follows:
Electronics
Inputs
Valves /
Outputs
24 V DC (2)
valves /
outputs
24 V DC (4)
logic
GND (3)
logic
GND (1)
valves /
outputs
Pin 1
Pin 4
1
2 3 4
-
+
-
+
Pin
Valves /
Outputs
Logic
inputs
Figure 7:
Power supply configuration
Figure 8:
Cutaway POWER connection
Pin 2 of the power supply must be supplied with a 4 A medium time-lag fuse; Pin 4 with 1 A.