Dip switch settings – Burkert Type 8640 User Manual
Page 49

49
BusModuleRioSlave(RIO/VA)
10.3.3. Output voltage not available
LED
Status
Description
U
0
FS
FN
OFF
FS and FN indicate fault type 4 and
failure number 1
Check supply voltage
10.4. DIP switch settings
NOTE!
Set the DIP switches through the film using a screwdriver (the film is very durable).
1
2
3
4
5
6
7
8
Address on the internal RIO bus
Mode inputs
Reserve always OFF
Terminating resistors
Changes made to the switch positions only take effect after the field bus module has been reset.
10.4.1. Address on the internal RIO bus: DIP switches 1 to 3
Each peripheral terminal has a unique address. This address is set on the valve terminal via DIP switches 1 to 3.
DIP 1
DIP 2
DIP 3
Address
Peripheral terminal
OFF
OFF
OFF
0
0
ON
OFF
OFF
1
1
OFF
ON
OFF
2
2
ON
ON
OFF
3
3
OFF
OFF
ON
4
4
ON
OFF
ON
5
5
OFF
ON
ON
6
6
ON
ON
ON
7
7
10.4.2. Mode inputs: DIP switches 4 and 5
NOTE!
The input modes allow the entries (feedback indicator) to be assigned in different ways in the process image of
the inputs (PAE).
DIP 4
DIP 5
No entries available
OFF
OFF
Normal mode
ON
OFF
Mode: shifted inputs
OFF
ON
Mode: halved inputs
ON
ON
CAUTION!
If there are no inputs available, both switches must be set to OFF.
english
Type 8640