Dip switch settings – Burkert Type 8640 User Manual

Page 49

Advertising
background image

49

BusModuleRioSlave(RIO/VA)

10.3.3. Output voltage not available

LED

Status

Description

U

0

FS
FN

OFF

FS and FN indicate fault type 4 and

failure number 1

Check supply voltage

10.4. DIP switch settings

NOTE!

Set the DIP switches through the film using a screwdriver (the film is very durable).

1

2

3

4

5

6

7

8

Address on the internal RIO bus

Mode inputs

Reserve always OFF

Terminating resistors

Changes made to the switch positions only take effect after the field bus module has been reset.

10.4.1. Address on the internal RIO bus: DIP switches 1 to 3

Each peripheral terminal has a unique address. This address is set on the valve terminal via DIP switches 1 to 3.

DIP 1

DIP 2

DIP 3

Address

Peripheral terminal

OFF

OFF

OFF

0

0

ON

OFF

OFF

1

1

OFF

ON

OFF

2

2

ON

ON

OFF

3

3

OFF

OFF

ON

4

4

ON

OFF

ON

5

5

OFF

ON

ON

6

6

ON

ON

ON

7

7

10.4.2. Mode inputs: DIP switches 4 and 5

NOTE!

The input modes allow the entries (feedback indicator) to be assigned in different ways in the process image of
the inputs (PAE).

DIP 4

DIP 5

No entries available

OFF

OFF

Normal mode

ON

OFF

Mode: shifted inputs

OFF

ON

Mode: halved inputs

ON

ON

CAUTION!

If there are no inputs available, both switches must be set to OFF.

english