Burkert Type 8640 User Manual
Page 31

31
Configurationandparameter
settingsforPROFIBUSDP
Example 4 - valve terminal with 16 valves (outputs) and 32 repeaters (inputs), every second repeat signal
not taken into account
• PROFIBUS-DP address 7
• The valves 1-8 are assigned to outputs (PAA) byte 17 in the process image.
• The valves 9-16 are assigned to outputs (PAA) byte 10 in the process image.
• Repeaters 1, 3, 5, ... 15 are assigned to inputs (PAE) byte 18 in the process image.
• Repeaters 1, 17, 19, ... 31 are assigned to inputs (PAE) byte 21 in the process image.
• Mode: Halved inputs
• Input filter active
DIP Switches
1
2
3
4
5
6
7
8
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
User parameter byte 11 User_Prm_Data 74 hex
Configuration:
Byte No. (slot)
1 (0)
2 (1)
3 (2)
4 (3)
Identification in Hex (Dec)
10 (016)
10 (016)
20 (032)
20 (032)
Process image output (PAA)
17
10
Process image input (PAE)
18
21
Allocation of inputs and outputs to control process image
Process image
Process image
Inputs (PAE)
Outputs (PPA)
Valve
Valve
Valve
Valve
Valve
Valve
Valve
Valve
Valve
Valve
Valve
Valve
Valve
Valve
Valve
Valve
Figure 17:
Allocation of inputs and outputs to control process image
english
Type 8640