Configurationandparameter

settingsforDeviceNet

12.

CONFIGURATION AND PARAMETER
SETTINGS FOR DEVICENET

12.1. Configuration of process data

To transmit process data via an I/O connection, there is one static input and one static output assembly available.
These assemblies contain selected attributes combined into one object so that process data can be transmitted
collectively via an I/O connection.

The process data can be accessed either cyclically in the connection variants 'polled I/O' and 'bitstrobed I/O' with
'change of state' when the input values vary, or acyclically via Explicit Messages. The access path for acyclical
access is:

class 4

instance 1
attribute 3

The output data can be read in acyclically via the Get_Attribute-Single service or written to acyclically via the
Set_Attribute_Single service.

4 data bytes for inputs (sensors or initiators)

3 data bytes for outputs (actuators or valves)

12.2. Configuration of the safety position of solenoid

valves if bus error

If a bus error occurs, the bus status LED may assume the "Green flashing", "Red flashing" or "Red" status.
(For a description see "Status of the Bus Status LED")

The objects Fault Action and Fault Value can be used to configure the solenoid valves in the event of a bus error.

If a bus fault occurs, the configuration data of the solenoid valves can be accessed acyclically via Explicit
Messages.

The service Get_Attribute_Single is available for read access to the configuration data and the service
Set_Attribute_Single is available for write access to the configuration data.
Object Fault Action (class 9 / instance 1-3 / attribute 5):

Determines the reaction of the outputs when a bus error occurs. Here, each output byte has an instance assigned
to it (in groups of 8 in each case).

Description

1

bin

On error the output retains its current state.

0

bin

On error the output is switched to the state laid down in the object Fault Value at the appro-
priate position.

Object Fault Value (class 9 / instance 1-3 / attribute 6):

Determines the state of the outputs when a bus error occurs. Prerequisite: Appropriate setting in Object Fault
Action. Here, each output byte has an instance assigned to it (in groups of 8 in each case).