19
FieldbusmodulePROFIBUSDP/V1
NOTE!
To ensure electromagnetic compatibility (EMC) connect the screw terminal FE (functional earth) to earth
potential using a short cable (30 cm).
Accessories
Plug-in connector (No. 918 226) for power supply (supplied).
8.1.2.
IP20 field bus connection
A 9-pole D-SUB connection is used for an IP20 protection class field bus connection. The following shows the
wiring layout according to Standard 19245 Part 1.
Pin-No.
Signal name (socket in device,
plug on cable)
Description
1
n.c.
-
2
n.c.
-
3
RxD/TxD-P
Receive / Send data P
4
CNTR-P (RTS)
Request to send (repeater control
signal)
5
DGND
Data reference potential
6
+5 V
Supply voltage - plus
7
n.c.
-
8
RxD/TxD-N
Receive / Send data N
9
n.c.
-