Applications object, English – Burkert Type 8640 User Manual
Page 58

58
FELDBUSmoduleDeviceNet
11.5. Applications object
Object
Class Instance Attribute
Access
Length
(byte)
Range
Default
Brief description
Assembly
4
1
3
Get
4
0 ... 0 x FF / per byte
-
4 byte inputs
Set
3
0 ... 0 x FF / per byte
0 x 00
3 byte outputs (valves)
Value
Outputs
9
1 ... 3
3
Get / Set
1
0 ... 0 x FF
0 x 00
Valve values
Fault Action
9
1 ... 3
5
Get / Set
1
0 ... 0 x FF
0 x FF
Action on fault or offline per
output
0: Fault Value (Def in Fault
Value Attr 6)
1: Hold last state
Fault Value
9
1 ... 3
6
Get / Set
1
0 ... 0 x FF
0 x 00
Factory ID
101
1
1
Get
4
Bürkert ident-number
Factory Serial
101
1
2
Get
4
Bürkert ident-number
Input
mode
150
1
1
Get / Set
1
0 ... 3
0: without
EME
1: with EME
0: no inputs
1: normal inputs
2: shifted inputs
3: halved inputs
Input filter
150
1
2
Get / Set
1
0 ... 1
1
0: Filter OFF
1: Filter ON
english