Nstallation – Burkert Type 8750 User Manual

Page 15

Advertising
background image

I

NSTALLATION

8750 - 13


Operating levels of the FMR
Operation of the FMR is done via the process operating level and via the configuration level.

The process operating level is active after
switching on the device. In this level, one can
switch between the AUTOMATIC and MANUAL
modes by briefly pressing the manual/automatic
key. In the AUTOMATIC mode, the position or
process control runs; in the MANUAL mode, the
valve may be opened or closed by hand. To
change to the configuration level, one must press
the M/A key for 5 s.

In the configuration level, the basic
functions and, if needed, supplementary
functions are specified on first
commissioning. During configuration,
the process falls into a stationary state
with the parameters immediately prior to
switchover. Return to the process level
is done from the menu item END.

Display and function keys

up down


FMR operation with

3 function keys
MANUAL/AUTOMATIC key
LED (yellow)
Manual → LED off
Auto → LED flashes
Arrow keys up / down

Key functions in the process
operating level for manual
(from automatic with

to manual)

open valve

close valve

+

fast opening

+

fast closing

Key functions in the configuration level
With key

you scroll up; with key

you scroll down or change the settings (values,

alternative parameters).
With key

you change between the menu levels, call up current settings in a menu item,

confirm entries, make changes and return to the menu item.

Factory settings and required operator settings
(factory settings are shown in italics, underlined, in the following operating menu)
Prerequisites - FMR is installed and connected;

- operating voltage and control pressure are switched on.

Procedure for checking and setting
After the operating voltage is switched on, there appears for ca. 5 sec the display EEPROM;
after this, the system automatically activates the process operating level with the display
POS 0.
The yellow LED in manual-automatic key

flashes and at the upper edge of the display, an

apostrophe (') rund from left to right.
To get to the configuration level, one presses the manual/automatic key

until the main

menu item ACT.FUNC is shown in the display (see following program sequence).

Advertising