Nstallation – Burkert Type 8750 User Manual

Page 17

Advertising
background image

I

NSTALLATION

8750 - 15

P.CO INP

INP P1'P2

Signal type P1'P2 (two pressure sensors),

alternatives to 4‘20A with

;

confirm setting with

and return

to P.CO INP

P.CO FILT

FILT 0

With arrow keys set a filter value

from 0 ... 9 for the process input; 0 = smallest effect;
9 = greatest effect; recommended setting: 5 or 6;
confirm setting with

and return to P.CO FILT

P.CO SCAL

DP 1

PV

000.0

PV

T

100.0

DP = decimal point for (0, 1, 2, 3) digits after the
point; PV = process value in m³/h; PV

= lower

scaling value (here 0 m³/h); is allocated to the
smallest input signal (here 4 mA);
PV

T

= upper scaling value (here 100 m³/h); is

allocated to the largest input signal (here 20 mA);
PV

T

must be actualized by the operator according to

the geometry of the control valve.

SP

xx.xx

SP

T

xx.xx

With SETP INT, menu item SP is suppressed
(only active with SETP EXT); SP = process setpoint
in m³/h
SP

= lower scaling value; is allocated to the

smallest value of the standard setpoint signal used
(0/4 mA; 0 V);
SP

T

= upper scaling value; is allocated to the

greatest value of the standard setpoint signal used
(20 mA; 5/10 V)

P.TYPFLOW

UNITM3/H

Select type of controlled variable; with the controlled
variable, the dimension is also specified;
alternatives: TYP FLOW (flow in m³/h) or TYP VELO
(flow velocity in m/s)

TEMP MAN

TEMP 20.0

Set with arrow keys, whether media temperature is
to be measured manually (TEMP MAN) or by
sensor (TEMP SENS); change of temperature (here
+20 °C) is possible with arrow keys

DENS 1.293

DIAM 0015

Medium density required for flow control; here
density for air of 1.293 kg/m³; specify DIAM for
piping diameter (here 15 mm), only possible with
TYP VELO active; confirm last setting with

;

program jumps to P.CO SCAL

P.CO TUNE

P.TUN ACT

P.TYPFLOW

The function P.TUN ACT must be active at the start
of PROCESSTUNE, only then can it be carried out
after completion of the required parameter entries;
change with arrow keys;
with

select the controlled member FLOW or

N.DEF (both define a PI controller)
with

confirm settings and return

to P.CO TUNE


Further to P.CO KV

Further to SIG--ERR