Nstallation – Burkert Type 8750 User Manual

Page 27

Advertising
background image

I

NSTALLATION

8750 - 25



Error message on execution of the function LEAK MEAS

Display

Cause of error

Remedy

L.ERR 1

No admission pressure at the controller unit
(> 50 mbar).

Switch on compressor before start of
leakage measurement.

L.ERR 2

Control does not fully close.

Execute AUTOTUNE.

• No leakage detectable:

the difference between admission
pressure and conveyance pressure is so
low, even at slight valve opening, that no
air leak can be measured.

• The leakage characteristic must be

deactivated since the precision of air flow
control cannot be raised.

L.ERR 3

• Leakage too great:

while the valve was being opened, the
conveyance pressure did not rise. Hence
no reference points for the characteristic
could be registered.

• Make sure that the conveying pipe is

closed and the blocking air is open.




Other malfunctions

Problem

Possible causes

Remedy

POS = 0 (for CMD > 0 %) or

Tight closure function CUTOFF

Deactivate

POS = 100 % (for CMD < 100 %)

has been activated inadvertently

tight closure function or

PV = 0 (for SP > 0) or

or no control air has been

connect control air

PV = PV

⊥

(for SP > SP

⊥

)

connected