Some acceptable ground sources, Phone company – DoorKing 1833 PC Programmable User Manual

Page 20

Advertising
background image

1835-065-E-7-13

18

The use of surge suppressors can significantly reduce the chance of component failure because of static charges or surges.
DoorKing recommends Installing a Phone Line surge suppressor (DoorKing P/N 1877-010 or equivalent) and a Low Voltage
surge suppressor (DoorKing P/N 1878-010 or equivalent) to help protect the entry system from power surges.

Proper grounding of this system is a requirement. To be effective, ground connections should be made with a minimum 12
AWG, 600 volt insulated wire to a ground point within 10 feet of the telephone entry system. The ground point must be at an
electrical panel, a metallic cold water pipe that runs in the earth, or a stainless steel grounding rod driven at least ten (10) feet
into the soil. A architectural style mounting post anchored to concrete does NOT make a good ground.

Install on each
16.5 VAC Transformer

Surge suppressor within 3 ft of ground source.

POWER LINE

1878-010

Low voltage surge suppressor

within 10 ft of entry system.

CALL

Z

A

Some Acceptable Ground Sources

Ground to a metallic cold water pipe.

Ground

Wire

Ground

Wire

Ground to an existing electrical system.

Electrical

Panel

Grounding rod 10 feet in soil.

IMPORTANT:

Ground wire shown without

safety protection for clarity. Make sure
ground wire is protected from being
touched or electrical shock could occur!

Phone line surge suppressor

within 10 ft of entry system.

CALL

Z

A

Surge suppressor within 3 ft of ground source.

Phone Company

PHONE LINE

1877-010

2.1.3 Grounding

2.1.4 Surge Suppression

2.1.5 Expansion Boards and Elevator Control

2.1.6 Ferrite Filter

If Expansion Boards are being used with this system, refer to the Installation and Wiring manual that came with the Expansion
boards, for detailed information on wiring Expansion boards to the PC programmable telephone entry system.

If Elevator Control is used with this system, refer to the Elevator Control Installation and Wiring manual for detailed information
on wiring the elevator control boards to this system and to the elevator push button control panel.

The Telephone Entry System comes with two (2) Ferrite Filters (1834 only comes with
one). These will help prevent noise and hum pickup in the phone lines. One is installed
around the 16 VAC power wires on the main terminal #19 and #20. The second is
installed around all the wires connected to the aux terminal.

To install the ferrite filter, release the
clip on the side to open the filter,
place the wires in the circular core
and snap the filter closed.

Power Wires

on all models

Auxiliary Wires

on 1833, 1835 and 1837 models

16A

C

20

19

18

17

16

15

14

16A

C

Main T

erminal

Aux T

e

rmi

nal

BA

T

1N

O

1N

C

2RY

2C

14

12

13

11
10

9
8
7
6
5
4
3
2
1

Clip Release

Clip Release

#1

#2

Phone Line Surge Suppressor

Low Voltage Surge Suppressor

Advertising
This manual is related to the following products: