Flow input – Liquid Controls SP4000 User Manual
Page 60

57
SP4000 Flow Computer
6.8
FLOW INPUT
(Continued)
FLOW INPUT
Select the type of square law flowmeter to be used with the
instrument.
Note:
This selection will only appear if one of the Square Law
selections were made in "FLOWMETER TYPE".
Selection:
ORIFICE, V-CONE, ANNUBAR, PITOT, VENTURI, FLOW
NOZZLE, BASIC SQRLAW/TARGET, WEDGE
Display:
ORIFICE
SQUARE LAW FLOWMETER
Select the type of measuring signal produced by the flowmeter.
Selection:
DIGITAL, 10 mV LEVEL
Voltage pulses, 10mV
trigger threshold.
DIGITAL, 100 mV LEVEL
Voltage pulses, 100mV
trigger threshold.
DIGITAL, 2.5 V LEVEL
Voltage pulses, 2.5V trigger
threshold.
4-20 mA
4-20 mA current signal
0-20 mA
0-20 mA current signal
4-20 mA STACKED
4-20 mA current signal
0-20 mA STACKED
0-20 mA current signal
0-5 V
0-5 V voltage signal
1-5 V
1-5 V voltage signal
0-10 V
0-10 V voltage signal
Display:
4-20 mA
INPUT SIGNAL
Set the low scale value for the analog input signal.
The value entered here must be identical to the value set for the
flowmeter.
Note:
• For flowmeters with analog/linear output, the flow computer
uses the selected system units for volumetric flowrate.
• The units for differential pressure flowmeters are
dependent on the system units selected for pressure:
- Imperial units [inches H2O]
- Metric units: [mbar]
Input:
Number with floating decimal point: 0.000...999999
Display:
.000 ft3/h
LOW SCALE VALUE
SQUARE LAW
FLOWMETER
INPUT SIGNAL
LOW SCALE