SP4000 Flow Computer

6.8
FLOW INPUT
(Continued)

FLOW INPUT

Select the type of square law flowmeter to be used with the
instrument.

Note:

This selection will only appear if one of the Square Law
selections were made in "FLOWMETER TYPE".

Selection:

ORIFICE, V-CONE, ANNUBAR, PITOT, VENTURI, FLOW
NOZZLE, BASIC SQRLAW/TARGET, WEDGE

Display:

ORIFICE
SQUARE LAW FLOWMETER

Select the type of measuring signal produced by the flowmeter.

Selection:

DIGITAL, 10 mV LEVEL

Voltage pulses, 10mV
trigger threshold.

DIGITAL, 100 mV LEVEL

Voltage pulses, 100mV
trigger threshold.

DIGITAL, 2.5 V LEVEL

Voltage pulses, 2.5V trigger
threshold.

4-20 mA

4-20 mA current signal

0-20 mA

0-20 mA current signal

4-20 mA STACKED

4-20 mA current signal

0-20 mA STACKED

0-20 mA current signal

0-5 V

0-5 V voltage signal

1-5 V

1-5 V voltage signal

0-10 V

0-10 V voltage signal

Display:

4-20 mA
INPUT SIGNAL

Set the low scale value for the analog input signal.
The value entered here must be identical to the value set for the
flowmeter.
Note:

• For flowmeters with analog/linear output, the flow computer

uses the selected system units for volumetric flowrate.

• The units for differential pressure flowmeters are

dependent on the system units selected for pressure:

- Imperial units [inches H2O]
- Metric units: [mbar]

Input:

Number with floating decimal point: 0.000...999999

Display:

.000 ft3/h
LOW SCALE VALUE

SQUARE LAW
FLOWMETER

INPUT SIGNAL

LOW SCALE