Relays – Liquid Controls SP4000 User Manual

Page 83

Advertising
background image

80

SP4000 Flow Computer

2

RATE

1

TOTAL

6.12
RELAYS
(Continued)

RELAYS

Enter a hysteresis value to ensure that the "ON" and "OFF"
switchpoints have different values and therefore prevent continual
and undesired switching near the limit value.

Input:

Number with floating decimal point:
0.000...999999

Display:

0.000 psia
HYSTERESIS

The alarm status for the particular relay can be cancelled here if (for
safety reasons) the setting "......, LATCH" has been selected in the
submenu "RELAY MODE". This ensures that the user is actively
aware of the alarm message.

Note:

• When in the HOME position, press the ENTER key to

acknowledge and clear alarms.

• The alarm status can only be permanently cancelled if the

cause of the alarm is removed.

Selection:

RESET ALARM? NO
RESET ALARM? YES

Display:

RESET? NO
RESET ALARM

As an aid during start-up, the relay output may be manually
controlled independent of it's normal function.

Selection:

NORMAL, ON, OFF

Display:

NORMAL
SIMULATE RELAY

HYSTERESIS

RESET ALARM

SIMULATE RELAY