Alarm sp lo 000xx °f, Mode hilo alarm mode lo alarm – Nova-Tech Digi-Sense Termperature Controller RS (Standard Models) User Manual
Page 14

11
LO Alarm
1. LO Alarm activates the alarm when the PV temperature drops below the
alarm temperature. Refer to Figure 12. If the Control Action is set to
HEAT and the PV temperature is below the alarm temperature when the
RUN Key is pressed, the alarm will not be activated. The PV tempera-
ture must first rise above the alarm temperature before the low alarm is
enabled. This allows for normal system startup without activating the
alarm.
FIGURE 13. LO ALARM SETTINGS SCREEN
HILO Alarm
1. HILO Alarm allows both a HI Alarm and LO Alarm to be set. Refer to the
HI Alarm and LO Alarm sections for a detailed description of the opera-
tion of each alarm. Refer to Figure 14.
ALARM SP
LO 000XX °F
FIGURE 14. HILO ALARM SCREEN
MODE
HILO ALARM
MODE
LO ALARM
FIGURE 12. LO ALARM MODE SCREEN
2. Select the LO Alarm screen by pressing the MENU key. The following
screen will appear (refer to Figure 13). Set the Process LO temperature
by using the arrow keys.