Audible Alarms
Audible Alarm permits the sound of an alarm. It has two options: On or Off.

Use the arrow keys to select an option and press the MENU key to advance

to the Advanced Setup MENU. Refer to Figure 17.

FIGURE 17. ALARM AUDIBLE SCREEN

AUDIBLE ALARM

ON

Advanced Set-Up

1. After pressing the MENU button, the ENTER ADVANCED SETUP screen

will be displayed (refer to Figure 18).

2. The flashing message YES will ask if you want to enter the Advanced

Screen. Press the MENU key as the word YES blinks.

NOTE:

If a change to that selection is not chosen within 3 seconds, the

program will automatically exit the setup mode.

ENTER ADVANCED

SETUP MENU YES

FIGURE 18. ADVANCED SETUP SCREEN

Sensor Calibrate

1. Sensor Calibrate enables the operator to calibrate out sensor error

to give a more accurate reading. Refer to Figure 19. Calibration

offset and PV (actual) temperatures are displayed.

2. To adjust the values in this option, the operator must know how

many degrees off the sensor is. To determine how far off the sensor

is, measure it against a secondary gauge known to be accurate.

3. Once the value is known, adjust the CAL offset value on the screen

using the arrow keys until the displayed temperature matches the

known temperature. Press the MENU key to advance to the Over

temp screen. (Refer to Figure 20.)