Appendix b – Nova-Tech Digi-Sense Termperature Controller RS (Standard Models) User Manual

Page 29

Advertising
background image

APPENDIX B

The following is a list of error messages that may be displayed by the Tem-

perature Controller and a description of corrective action.

Upper

Lower

Display

Display

Action

normal

OVER TEMP STOP

PV exceeded OVER TEMP

STOP setting in user setup.

normal

LOOP BREAK STOP

No change in PV with output

on for user settable time

period. Adjust LOOP BREAK

STOP in user setup.

normal

OPEN PROBE STOP

Detected open probe sensor

while running. Check probe.

normal

OVER PROBE STOP

PV exceeded the upper limit of

selected probe type.

normal

UNDER PROBE STOP PV went below lower limit of

selected probe type.

NO OUTPUT

CHECK 10 A

No AC voltage detected at the

POWER

FUSE

heater output. Check the

heater/cooler output fuse. If

fuse is OK, return unit for

service.

INTERNAL

SERVICE

Return unit to your dealer.

ERROR #

REQUIRED

B-1