Sensor offset cal ±±±±± xx.x xxx.x °f, Over temp. stop xx °f above sp, Loop break stop xxx.x minutes – Nova-Tech Digi-Sense Termperature Controller RS (Standard Models) User Manual

Page 17

Advertising
background image

14

SENSOR OFFSET

CAL

±±±±±

XX.X XXX.X °F

FIGURE 19. SENSOR OFFSET CAL

NOTE:

Calibration can also be done using an ice bath or boiling water

and adjusting the offset until 32.0 °F or 212 °F is displayed.

Over Temp Stop

1. Over temp stop temperature, a safety feature, is added to the setpoint

(SP) temperature. If the PV temperature exceeds this amount, the tem-

perature controller will stop. Over temp stop does not operate if the

COOL control action is selected. Refer to Figure 20.

OVER TEMP. STOP

XX °F ABOVE SP

FIGURE 20. OVERTEMP SCREEN

2. To change the Overtemp value, use the arrow keys. After the value has

been set, press the MENU key to advance to the Loop Break Stop Screen.

Loop Break Stop
Loop break stop, a safety feature, is designed to stop the temperature

controller if the heater output is on for the amount of time set in Loop Break

Stop and the PV temperature does not increase more than 1.0 °F. If the

COOL control action is selected, it is stopped if the PV temperature does not

decrease more than 1.0°F. Refer to Figure 21.

LOOP BREAK STOP

XXX.X MINUTES

FIGURE 21. LOOP BREAK STOP SCREEN