Control Mode On/Off

1. The Control Mode On/Off turns off the output when the actual tempera-

ture exceeds the setpoint (heat control action). The output will turn on

when the actual temperature falls below the setpoint temperature minus

the hysteresis temperature. Refer to Figure 24.

ON/OFF CONTROL

HYSTERESIS XX.X °F

FIGURE 24. ON/OFF CONTROL HYSTERESIS SCREEN

2. Adjust the hysteresis value on this screen using the arrow keys.
3. Press the MENU key to advance to the RUN TIME Screen.

PID - Proportional Band, Integral and Derivative

PID is the means of selecting the response speed or sensitivity of a propor-

tioned controller to achieve stability in the system. It should be used when

system stability or accuracy requirements are too great for use of on/off control.

AUTO Tune

1. After selecting the PID screen the next screen to appear will be AUTO

TUNE. Refer to Figure 25. Two choices are available for this selection:

AUTO TUNE ENABLED and AUTO TUNE DISABLED. The recommended

choice for this screen is AUTO TUNE ENABLED.
The default setting is ENABLED. Use the DOWN arrow key to select

either enabled or disabled. Press the MENU key to enter your selection.

NOTE:

When AUTO TUNE DISABLED is selected, auto tuning cannot be

initiated using the TUNE key on the front panel.

AUTO TUNE

ENABLED

FIGURE 25. AUTO TUNE SCREEN