Control action heat, Control mode pid – Nova-Tech Digi-Sense Termperature Controller RS (Standard Models) User Manual

Page 18

Advertising
background image

15

Loop break stop is designed to terminate the process currently running if the

process is interrupted for a preset period of time. The loop break stop senses

that nothing is happening in the process and turns the process off.
Enter an elapsed time using the UP and DOWN arrow keys. For slow sys-

tems, a longer time should be entered.

Control Action

1. The Control Action screen allows selection of the type of process that will

be performed; either HEAT or COOL. Refer to Figure 22. In the heat

mode, the output is on when the actual temperature is below the setpoint

temperature (inverse action). In the cool mode, the output is on when the

actual temperature is above the setpoint temperature (direct action).

CONTROL ACTION

HEAT

FIGURE 22. CONTROL ACTION SCREEN

2. The default setting is HEAT. Use the DOWN arrow key to select either

heat or cool actions. Press the MENU key to enter your selection.

Control Mode

1. The Control screen has two options: PID (proportional band, integral

and derivative), and ON/OFF. Refer to Figure 23.

CONTROL MODE

PID

FIGURE 23. CONTROL SCREEN

2. Select one of these options using the arrow keys. When the desired

option appears on the screen, press the MENU key. Refer to the PID

procedural paragraphs, following, for additional information.