Installation

33

F232102

The power cable should be disconnected by one of two
methods. Either a plug socket combination that is
interlocked with a combined switch or a fixed
disconnect that provides relief from mechanical strain
on connection points should be used. Both methods
must comply with the authority having jurisdiction at

the point of installation and/or the National Electric
Code, article 400-5, EN60204 section 15.4.3. The
service disconnect mechanism should be between
2 and 6 feet (0.6 to 1.9 m) above the floor and should
be easily accessible.

Cabinet Freestanding

Electrical Specifications

Voltage Designation

Standard

Electric Heat

M

ode

l

Code

Vo
lt

a

g

e

Cyc

le

P

h

ase

Wi
re

Full Loa

d

Am

p

s

Cir
c

uit

Br
eake

r

A.W

.G.

mm

2

Full Loa

d

Am

p

s

Cir
c

uit

Br
eake

r

A.W

.G.

mm

2

135

N

440 – 480

50-60

3

3

15

30

10

3x4

78

95

4

3x25

P

380 – 415

50-60

3

3

15

30

10

3x4

78

95

4

3x25

Q

200 – 240

50-60

3

3

29

60

6

3x16

N/A

250

N

440 – 480

50-60

3

3

28

40

8

3x10

N/A

P

380 – 415

50-60

3

3

32

40

8

3x10

N/A

Q

200 – 240

50-60

3

3

56

70

6

3x16

N/A

NOTE: Wire sizes shown are for copper, THHN, 90° conductor per NEC article 310.