INSTALLATION

FTA-IOM-2013-0227

SECTION 2

2-8

gas at 11“w.c. is required. For details contact a local
liquid propane dealer.

Instrument Air

Instrument air provision for pneumatically actuated
control devices should meet the minimum and
maximum fl ow rate and delivery pressures specifi ed by
the individual equipment. Additionally, it should be a dry,
dust free supply with a dew point of -40 F (-40 C).

Electrical Supply

Adhere to the following for electrical supply installation:

1. Install wiring and ground in equipment in

accordance with authority having jurisdiction
or in absence of such requirements the National
Electrical Code, ANSI/NFPA 70.

2. Provide a wall-mounted, fused disconnect sized for

the unit. This must be fi tted by the client/contractor
if disconnect is not supplied on the panel.

3. Size fuses according to motor name plates and

local electrical codes.

4. Connect power to the terminal strip as supplied on the

inside of the panel box.

NOTE: Single skid systems are generally shipped completely

prewired.

NOTE: The liquid level switch on the expansion tank, when

supplied, will be shipped in the parts box and must be
installed in the fi eld.

5. Determine multiple skid systems wiring requirements

(between the skids). Fulton will run conduit and wire
the devices on each skid. For the devices that have to
come down for shipping, the wire will be left at the end
of the conduit where possible and wired in the fi eld (by
others). When the system has multiple skids that are
adjoining, the conduit will be installed to break at the
skid joints. The wire for the conduit running between
the skids will be shipped loose to prevent damage
when the skids are put back together. These wires
will need to be run by the installing contractor in the
fi eld and wired to proper locations. If there is wiring
between skids that are not adjoining, then this will need
to be done by qualifi ed personnel.

FIGURE 3 - TYPICAL GAS-FIRED MODULATED CSD-1 FUEL TRAIN

1” Gas Connection

Manual
Gas Valve

Manual
Gas Valve

Gas Pressure
Regulator

Diaphragm
Gas Valves

Butterfly
Valve

Pilot Gas
Valve

Pilot Gas
Regulator

Manual
Ball Valve