Maintenance – Fulton Vertical Tubeless (FT-A) Thermal Fluid (hot oil) Heater User Manual

Page 75

Advertising
background image

Questions? Call (315) 298-5121, or visit us online at www.fulton.com

SECTION 4

FTA-IOM-2013-0227

MAINTENANCE

4-15

TABLE 10-J - HIGH GAS PRESSURE SWITCH TROUBLESHOOTING

Problem

Potential Remedy

Gas pressure setting

on the main regulator

is too high

With unit running at high fi re, make sure that the modulated gas valve is at full open.

Since unit lights at low fi re, it may be necessary to increase high gas pressure setting or jumper contacts to allow unit

to modulate to where modulation gas valve back pressure is lessened.

Check net last elbow gas pressure and compare to factory test fi re sheet. Net gas pressure is running gas pressure

minus p urge pressure. Make sure net pressure reading is within .2” w.c. of factory reading. If there is a diff erence,

adjust main regulator. Adjust for proper combustion throughout range.

Low fi re gas valve

setting is too low

Because the sensing point of the High Gas Pressure Switch is upstream of the modulating gas valve, the highest

pressure read will occur during low fi re.

Check net last elbow gas pressure and compare to factory test fi re sheet. Net gas pressure is running gas pressure

minus purge pressure. Make sure net pressure reading is within .1” w.c. of factory reading. If there is a diff erence,

adjust modulating gas valve linkage. Adjust for proper combustion throughout range.

Gas pressure switch

setting is improper

If above two items are proper, check the pressure that the high gas pressure switch is sensing by way of a tee

installed in the line. Hold unit at low fi re and check pressure. Setting on switch should be 10% over pressure read. Call

Fulton if you have any questions.

Gas regulator has

failed open

This is highly unlikely. Regulators will usually fail safe in the closed position. The gas regulator can be checked by

checking upstream pressure and comparing to downstream pressure. Make sure that the upstream pressure is not

above the rating of the regulator. Make sure that the downstream pressure does not exceed the range of the spring.

If regulator has failed, replace, reset input and adjust input throughout the range.

TABLE 10-K - LOW GAS PRESSURE SWITCH TROUBLESHOOTING

Problem

Potential Remedy

Gas pressure setting

on the main regulator

is too low

At high fi re, the modulating gas valve is full open resulting in the least amount of back pressure in the gas train. With

unit running at high fi re, check net last elbow gas pressure and compare to factory test fi re sheet. Net gas pressure

is running gas pressure minus purge pressure. Make sure net pressure reading is within .2” w.c. of factory reading. If

there is a diff erence, adjust main regulator. Adjust for proper combustion throughout range.

Gas orifi ce plate is

damaged

If the orifi ce plate is damaged, it may be holding back less gas creating a lower pressure on the sensing switch. Pull

burner and inspect gas orifi ce plate. Plate should in no way be warped or degraded. If it is, replace. After reinstallation,

recheck input and adjust combustion throughout range.

Gas regulator has

failed closed

Regulators will usually fail safe in the closed position. The gas regulator can be checked by checking upstream

pressure and comparing to downstream pressure. Make sure that the upstream pressure is not above the rating of

the regulator. If regulator has failed, replace, reset input and adjust input throughout the range.

TABLE 10-L - LOW OIL PRESSURE SWITCH TROUBLESHOOTING

Problem

Potential Remedy

Fuel oil pump may

have lost its prime

An air bubble in the pump will result in a momentary loss of prime that will be enough to cause the Low Oil Pressure

Switch to trip. Ensure that oil pump is primed properly and all connections are tight. Check the pump seal. A blown

seal will allow air in the pump housing.

Fuel oil pump motor

may have failed

Check the pump motor for proper voltage. If voltage is proper but motor does not turn, replace or rebuild motor. If

there is no voltage, check motor starter for input signal and incoming 3-phase power.

Fuel oil pump coupling

may have failed

A failed coupling will result in the pump not turning. Check coupling. Replace if necessary..