Installation – Fulton Vertical Tubeless (FT-A) Thermal Fluid (hot oil) Heater User Manual

Page 30

Advertising
background image

© The Fulton Companies 2013

INSTALLATION

FTA-IOM-2013-0227

SECTION 2

2-24

!

WARNING

All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.

4

CAUTION

If the deaerator/thermal buff er/
expansion tank is located outdoors, a
nitrogen blanket is required.

1. An automatic venting device must be fi tted to the system expansion tank.

Consult Fulton Thermal Corporation for further details.

2. The location for the liquid level switch (Figure 14) is a 2-1/2” NPT connection

on the same end of the tank as the inlet. The liquid level switch is supplied
and shipped with the unit, and must be installed by the customer and then
wired to the control panel.

3. If the tank is located outdoors, nitrogen is required.

Model

Capacity

(gallons)

Initial Fill

(gallons)

Available for

Expansion

(gallons)

Max System

Volume

FT-200-L

52

25

46

184

FT-500-L

132

40

121

525

FT-1000-L

264

80

232

1000

FT-1500-L

397

90

380

1400

FT-2000-L

528

145

444

1700

FT-3000-L

793

215

717

2600

FT-5000-L

1310

300

1168

4600

FIGURE 12 - EXPANSION TANK DETAILS

Hot Fluid

Medium Fluid

Cool Fluid

Gases (Steam)

Fluid In

Liquid

Level

Switch

Fluid Out

Drain

Vent for Piping

to Safe Catchment

Expansion

Tank

Deaerator

Section

Thermal

Buffer Section

Expansion

Volume