FEC AFC1100 User Manual

Page 21

Advertising
background image

)(& ,QF

4.10 Axis Unit DIP Switch setting.

In a multi-Axis AFC1100 system, it is necessary to number the Axis units sequentially
beginning from 1. The number is set using the DIP switch located at the side of the Axis unit.

FIG. 4-10 Dip Switch settings

4.10.1 Axis Unit DIP switch positions 1 ~ 3

{ DIP switch positions 1 ~ 3 are used for setting the special configuration features as defined

in the following explaination

{ DIP Switch 1 -

Calibration acceptance window selection.
Software version 1.09 and greater

P On - Calibration acceptance = +/- 10 % of Full scale torque

P Off - Calibration acceptance = +/- 4 % of Full scale torque

{ DIP Switch 2 -

RS422 communications port configuration
Software version 1.14 and greater

P On - Raw data output mode. (Data Dump)

P Off - User console communications mode.

{ DIP Switch 3 -

Start input type selection.
Software version 1.11 and greater

P On - Deadman - Start input must remain on for the entire cycle.

P Off - Normal mode - Start input pulse initiates automatic cycle.

Chapter 4: System Setup and Wiring (Rev. 8/98)

Page 4-21