Finish Thompson SP22 Series Self-Priming User Manual

Page 8

Advertising
background image

8

CAUTION: Do not operate the pump to check rotation until
the pump is full of liquid

Check all electrical connections with the wiring diagram on
the motor Make sure the voltage, frequency, phase and amp
draw comply with the supply circuit

To verify correct rotation of the motor:

1 Install the pump into the system

2 Remove the fill plug and fill the housing with (2 1/2) US

gallons (9 5 liters) of the service liquid or water Replace fill

plug and tighten until the o-ring is seated

3 Fully open the suction and discharge valves

4 Jog the motor (allow it to run for 1-2 seconds) and observe

the rotation of the motor fan Refer to the directional arrow

molded into the front of the housing if necessary

NOTE: An SP pump running backwards may not prime

Section III - Start-up and Operation

1 Be sure the housing has been filled with 2 1/2 gallons (9 5

liters) of service liquid and the fill plug has been installed

and tightened until the o-ring is seated

2 Open the inlet (suction) and discharge valves completely

3 Turn the pump on Wait for discharge pressure and flow

to stabilize (could take several minutes depending upon

suction lift) Adjust the flow rate and pressure by regulating

the discharge valve Do not attempt to adjust the flow with

the suction valve

Section IV - Shutdown

Turn off the motor
NOTE: When the pump is stopped without a check valve in the
piping, liquid will flow through the pump returning to the suction
source The SP design allows enough liquid to be retained in the
housing to allow repriming without having to refill with liquid
Flush Systems

CAUTION: Some fluids react with water; use compatible

flushing fluid

1 Turn off the pump
2 Completely close the suction and discharge valves
3 Connect flushing fluid supply to flush inlet valve
4 Connect flushing fluid drain to flush drain valve
5 Open flushing inlet and outlet valves Flush system until the

pump is clean

NOTE: The drain can be used as the flushing drain valve using
appropriate customer supplied fittings Using the drain helps to
promote superior flushing and draining results

strainer must be periodically cleaned to prevent restriction

Strainer hole size should be 1/8” (1 6 mm) with the amount

of open area equal to or greater than 2 times the suction

pipe diameter

• It is recommended that a vacuum/pressure gage be installed

in the suction piping

• For faster priming on installations with high lift, a foot valve

is recommended

• Check and control valves (if used) should be installed on

the discharge line The control valve is used for regulating

flow Isolation valves on the suction and discharge are used

to make the pump accessible for maintenance The check

valve helps protect the pump against damage from water

hammer This is particularly important when the static

discharge head is high

NOTE: If a check valve is used in the discharge line, it must

be placed at a distance at least equal to the maximum suc-

tion lift from the pump If this cannot be done, an air vent

must be provided in the discharge line

• If flexible hose is preferred over pipe, use a reinforced hose

rated for the proper temperature, pressure and is chemically

resistant against the fluid being pumped

• The suction valve must be completely open to avoid

restricting the suction flow

• When installing pumps with flanges, we recommend use of

low seating stress gaskets such as Gore-Tex

®

or Gylon

®

(expanded PTFE)

• It is advisable to install a flush system in the piping to

allow the pump to be flushed before the pump is removed

from service

NOTE: The pump is provided with a 1/2” BSPP drain in the

impeller housing

• A “tee” can be installed in the discharge piping as an

alternative location for filling the housing with fluid before

pump operation

• “Filling” is defined as filling the housing with 2 1/2 gallons

(9 5 liters) of liquid

• “Priming” is defined as evacuating all the air from the

suction piping/pump and replacing it with fluid

Motor/Electrical
Install the motor according to NEC requirements and local
electrical codes The motor should have an overload
protection circuit

Wire the motor for clockwise rotation when facing the fan
end of the motor

Advertising