1. Specifications Check

18

1.3 Operating conditions

1.3.1 Available Conditions for Operation

When selecting a desired model of linear servo actuator (small type / flat type), you must ensure

that the selected actuator satisfies the following two conditions.

[Condition 1]

The thrust required for acceleration must not exceed the maximum thrust of the linear servo

actuator.

[Condition 2]

The thrust during continuous operation must not exceed the rated thrust of the linear servo actuator.

The above conditions are explained by using a trapezoid operation as an example.

Speed

Time

The above operation pattern can be expressed differently in a graph where the vertical axis

represents thrust.

Time

Thrust

t : Operation time per cycle (sec)

ta : Acceleration time (sec)

tf : Moving time at constant speed (sec)

td : Deceleration time (sec)

Fa : Thrust required for acceleration (N)

Ff : Traveling resistance (N)

Fd : Thrust required for deceleration (N)