Pay due attention to the environment in which the controller is installed.

3.1 Installation Environment

The controller can be used in a pollution degree 2

*1

or equivalent environment.

*1 Pollution degree 2: Normally, only non-conductive pollution occurs. However, a temporarily electricity

conductive pollution caused by condensation may be expected (EN60947-5-1).

(1) When installing and wiring the controller, do not block the cooling vent holes. (If sufficient ventilation is

not provided, not only the controller is unable to demonstrate its designed performance, but it may
also cause unexpected breakdown.)

(2) Prevent foreign objects from entering the controller through vent holes. The controller is not

constructed dustproof or waterproof (oilproof). Accordingly, avoid using the controller in a dusty place
or place subject to oil mist or cutting fluid.

(3) Do not expose the controller to direct sunlight or irradiated heat from heat treatment ovens or other

large heat sources.

(4) Use the controller in an environment of 0 to 40

qC in surrounding air temperature and 85% or below

(non-condensing) in humidity, free from corrosive or natural gases.

(5) Use the controller in an environment where it will not be subject to external vibration or shock.
(6) Prevent entry of electrical noise into the controller or its cables.

3.2 Supplied Power

The supplied power is 24 VDC

r 10%.

(Maximum power-supply current: 300 mA)

3.3 Noise Elimination and Grounding

This section explains how to eliminate noise in the controller during use.

(1) Wiring and power supply

[1] Provide dedicated class D grounding. The grounding wire should have a wire size of 1.6 mm

2

or

larger.

Simple
absolute unit

Other

equipment

Connect to ground
using a cable of the
largest size over the
minimum distance.

Metal

enclosure

Class D grounding
(Formerly class 3 grounding: Grounding
resistance of 100

: or less)

Simple absolute

unit

Other

equipment

Connect the grounding wire to
one controller at a time without
sharing it with or connecting via
other devices.