RS232 Communications

The RS-232 interface uses a 9-pin female D-sub connector. Information provided includes data about
utility, load and the UPS. The interface port pins and their functions are identified in the following table:

PIN #

FUNCTIONS

1,4,6,7,8,9

Reserved

2

UPS transmit

3

UPS receive

5

Ground

SNMP Communications Option

The UPS provides an intelligent slot for internal or external network card. This special intelligent network
card can be compatible with popular software and hardware found on the web and in operating
systems. It can support operating systems such as HP Open View, IBM Netview, SUN Netmanager, etc.
This enables the UPS to provide instant UPS and power information over the network. Please contact
your reseller for additional details.

Emergency Power Off (EPO) Port

A customer supplied switch located remotely can be used to close the EPO connection and allows the
UPS output receptacles to be switched off. Since the EPO shuts down the equipment immediately,
orderly shutdown procedures are not followed by any power management software. The UPS will have
to be manually restarted in order to regain power to the outlets on the UPS.

Keep Pin 1 and Pin 2 closed for UPS normal operation. To activate EPO function, cut the wire between
Pin 1 and Pin 2.