UNINTERRUPTIBLE POWER SUPPLY (UPS)

Xtreme Power Conversion Corporation (Rev 8/29/13)

Page 38

Symptom

Possible cause

Remedy

The icon

and

are

flashing on LCD display and alarm is
sounding twice every second.

UPS is in overload.

Remove excess loads from
UPS output.

UPS is in overload. Devices
connected to the UPS are
being fed directly from the
electrical utility via the
Bypass

Remove excess loads from
UPS output.

After repetitive overloads,
the UPS is locked in the
Bypass mode. Connected
devices are being fed directly
by the electrical utility.

Remove excess loads from
UPS output, then shut down
the UPS and restart.

Fault code is shown as 43 and the
icon

is showing on LCD

display and alarm is sounding
continuously.

The UPS shut down
automatically because of the
overload condition on the
UPS output.

Remove excess loads from
the UPS output and restart
the UPS.

Fault code is shown as 14 and alarm
is sounding continuously.

The UPS shut down
automatically because short
circuit occurs on the UPS
output.

Check output wiring and if
connected devices are in
short circuit status.

Fault code is shown as 01, 02, 03, 04,
11, 12, 13 and 41 on LCD display and
alarm is sounding continuously.

A UPS internal fault has
occurred. There are two
possible results:

1. The load is still

supplied, but directly
by AC utility via
bypass.

2. The load is no longer

supplied with power.

Contact your dealer for
support.

Battery backup time is shorter than
expected.

Batteries are not fully
charged.

Charge the batteries for at
least 5 hours and then re-
check capacity. If the problem
still exists, contact your
dealer for support.

Batteries are defective.

Contact your dealer for
battery replacement.