UNINTERRUPTIBLE POWER SUPPLY (UPS)

Xtreme Power Conversion Corporation (Rev 8/29/13)

Page 37

TROUBLESHOOTING

If the UPS does not operate correctly, please use the table below to troubleshoot the problems.

Symptom

Possible cause

Remedy

No indication and alarm even though
the utility is normal.

The AC input power is not
connected well.

Check if input power cord is
firmly connected to the
utility.

The AC input is connected to
the UPS output.

Plug the AC input power cord
into the AC input utility
correctly.

The icon

and the warning code

flash on LCD display and alarm

sounding every second.

EPO function is enabled.

Set the circuit to the closed
position to disable EPO
function.

The icon

and

are flashing

on LCD display and alarm is sounding
every second.

Line and neutral conductors
of UPS input are reversed.

Have a qualified electrician
correct the input receptacle
wiring.

The icon

and

are

flashing on LCD display and alarm is
sounding every second

The internal battery is
incorrectly connected.

Check to make sure all
batteries are properly
connected.

Fault cod is shown as 27 and the icon

is showing on LCD display and

alarm is continuously sounding.

Battery voltage is too high or
the charger is in fault
condition.

Contact your dealer for
support.

Fault cod is shown as 28 and the icon

is showing on LCD display and

alarm is continuously sounding.

Battery voltage is too low or
the charger is in fault
condition.

Contact your dealer for
support.