SPECIFICATIONS

120V MODEL

P90-1000

P90-1500

P90-2000

P90-3000

INPUT

Voltage

120 VAC (85-150V) @ full load

Capacity VA (W)

1000 VA

(900 W)

1500 VA

(1350 W)

2000 VA

(1800 W)

3000 VA

(2700 W)

Frequency

40 - 70 Hz

Power Factor

≥ 0.99 @ normal voltage @ full load

Topology

Online

ECO Mode

Increases efficiency to 98%

EPO

Normally closed

OUTPUT

Voltage

120 VAC ± 1% battery mode (adjustable to

100/110/115/120VAC)

Frequency

57 - 63 Hz

THD (full load)

≤ 2% linear load (8% max battery mode before shutdown)

Wave form

Sine wave, 0 ms transfer time

Load Power Factor

0.9

Efficiency

86-88% (AC mode); 83-85% (Battery mode)

Auto Restart

Yes

Start on Battery

Yes

Rated Current

8.3A

12.5A

16.67A

25.0A

Overload Capacity

125% for 2 min; 150% for 10 sec; > 150% 1 sec

Crest Factor

5:1 at full load

BATTERY

Battery Type

(2) 12V 9AH

/ 24V

(3) 12V 9AH /

36V

(4) 12V 9AH

/ 48V

(6) 12V 9AH

/ 72V

sealed maintenance-free in hot-swappable trays

Backup Time

3 min 45 sec

4 min 41 sec

3 min 50 sec 4 min 15 sec

Charge Current

1A

Recharge Time

< 4 hours to 90%