KB Electronics KBDA-42 User Manual

Page 19

Advertising
background image

6.1

AC LINE INPUT CONNECTION (see Warning, on page 17) – Connect the AC line input to

Terminal Block TB1. See Electrical Ratings, Table 3, on page 10.

Application Note: If operation with a Ground-Fault Circuit-Interrupter (GFCI) is required, see

Function No. 0.04, on page 32.

Note: The rated AC line voltage of the drive must match the actual AC line input voltage. On

Models KBDA-24D, 27D, the setting of Jumper J1 must match the AC line input voltage.

AC Line Fusing –

The drive does not contain line fuses. Most electrical codes require that each

ungrounded conductor contain circuit protection. Do not fuse neutral or ground connections.

It is recommended to install a fuse (Littelfuse 326, Buss ABC, or equivalent) or a circuit breaker

(Square D QOU or equivalent) in series with each ungrounded conductor. Do not fuse motor

leads. For the recommended fuse size, see Table 3, on page 10.

Connect the drive in accordance with the National Electrical Code requirements and other local

codes that may apply to the application.

Model KBDA-24D –

Terminals “L1”, “L2” –

Designed for single-phase

AC line input only. Rated for

208/230 Volt AC line input

with Jumper J1 set to the

“230V” position (factory set-

ting) and rated for 115 Volt

AC line input with Jumper

J1 set to the “115V” posi-

tion. See Figure 10.

Note: 230 Volts AC will be

applied to the motor with

115 Volt AC line input.

Model KBDA-27D – Terminals “L1”, “L2” – Designed for single-phase AC line input only. Rated

for 208/230 Volt AC line input with Jumper J1 set to the “230V” position (factory setting) and rated

for 115 Volt AC line input with Jumper J1 set to the “115V” position. Rated for 1

1

2

HP maximum

with 115 Volt AC line input and 2 HP maximum with 208/230 Volt AC line input. See Figure 10.

Note: 230 Volts AC will be applied to the motor with 115 Volt AC line input.

Model KBDA-29 – Terminals “L1”, “L2”, “L3” – Designed for single-phase or 3-phase AC line

input. Rated for 208/230 Volt AC line input only. Rated for 2 HP maximum with single-phase AC

line input (Terminals “L1”, “L2”) and 3 HP maximum with 3-phase AC line input (Terminals “L1”,

“L2”, “L3”). See Figure 11, on page 19.

Models KBDA-45, 48 – Terminals “L1”, “L2”, “L3” – Designed for 3-phase AC line input only.

Rated for 400/460 Volt AC line input only. See Figure 11, on page 19.

18

TABLE 4 – DRIVE TERMINAL BLOCK WIRE AND TIGHTENING TORQUE SPECIFICATIONS

Terminal Block

Description

Model

Maximum Wire Size (Cu) Recommended Tightening Torque

AWG

mm

2

in-lbs

kg-cm

TB1

AC Line Input and Motor

Connections

KBDA-24D

12

3.3

7

8

KBDA-27D, 29, 45, 48

12

3.3

12

14

TB2

Run/Fault Output Relay Contacts

All

16

1.3

3.5

4

*Model KBDA-27D is rated for 11⁄2 HP maximum with 115 Volt AC line input and 2 HP

maximum with 208/230 Volt AC line input.

FIGURE 10 – MODELS KBDA- 24D, 27D*

AC LINE INPUT, MOTOR, AND GROUND CONNECTIONS

Ground

Motor

(Earth)

115, 208/230 Volt

AC Line Input

Single-Phase

Ground

(Earth)

MOTOR

U

V

TB1

W

L1

L2

AC LINE

Advertising
This manual is related to the following products: